Generator charging calculator

Enter the nameplate data – the calculator estimates how much charging power really reaches the battery during hours of charging, and how to set your charger.


      Frequently asked questions about charging with a generator

      Why does my generator charge less than the nameplate says?

      When charging batteries, the generator runs at full load for hours. The nameplate figure is often a short-term or peak value, and reactive power and charging losses come on top. Realistically, 60–80 % of the nameplate power is typical. That is physics, not a defect.

      What is the difference between kVA and kW?

      kVA is the apparent power the generator has to handle, kW the usable real power. The difference is reactive power – like the foam in a beer glass. Victron states a power factor of 1 for the charger in the MultiPlus-II; simple chargers typically have 0.6–0.8. A 4 kVA generator then often delivers only about 3 kW.

      What do Max., PRP and COP mean on the datasheet?

      Max. or standby is a short-term value, e.g. for starting an appliance. PRP (prime power) applies to varying load averaging about 70 %. COP is the continuous rating for hours of load – that is the value that counts for battery charging. Many manufacturers do not state it at all.

      Which generator is best for charging batteries?

      Inverter and DC generators: clean voltage, less fuel. Synchronous generators with a voltage regulator (AVR) are about 80–90 % usable; simple generators without a voltage regulator – asynchronous or self-excited synchronous, like many welding and site generators – only about 60–70 %, because the voltage fluctuates strongly under load.

      How do I set my Victron charger on a generator?

      Limit the AC input current (“AC input current limit”) to approx. 70 % of the nameplate current, or approx. 80 % for generators with AVR. The UPS function must be switched off when running on a generator. The calculator shows the right value for your generator. Important: with PowerAssist enabled, every MultiPlus, Quattro and EasySolar has a minimum configurable input current – the larger the unit, the higher it is. Check this value with the manufacturer or your supplier before choosing a small generator. As a safe rule of thumb, Victron recommends a generator about 60–70 % larger than the Multi (e.g. 5 kVA for a 3000 VA Multi), and about another 30 % more for an inverter generator. Smaller generators work if the input and charge current are limited accordingly.

      Why does an inverter generator need more reserve, and what helps with load peaks?

      A generator with a voltage regulator (AVR) buffers short load peaks with its rotating mass, and when overloaded it audibly struggles. An inverter generator is limited electronically: when overloaded it switches off its output while the engine keeps running. It then looks as if it is charging although nothing arrives. That is why the right size matters even more for an inverter generator – Victron recommends it about 30 % larger than an equivalent AVR model. Against load peaks you can also enable the dynamic current limiter on the MultiPlus, Quattro and EasySolar: the Multi takes over the load step and loads the generator only gradually. Note: it is ignored when the ESS assistant is installed, so it only works without ESS.

      Can I use a three-phase generator for charging at 230 V?

      Yes, but continuously only with about a third of its power, because the charger is connected to a single phase. Example Mosa GM 7/200: 6.5 kVA PRP three-phase, i.e. 9.4 A per phase. The 230 V socket is rated at 17.4 A, but during hours of charging it held only about 8 A in our test; above that the socket’s thermal protection kept briefly dropping the load. Mosa recommends the auxiliary output for welding tools, not for continuous loads. So limit the charge current to the phase current – choose “three-phase – charging on one phase” in the calculator.

      How much fuel does a generator use per kWh?

      Guide values per kWh generated: simple petrol generator at half load 0.65–0.75 l, near continuous power 0.5–0.6 l, inverter generator 0.4–0.5 l, DC generator or modern diesel 0.3–0.45 l. Half load is expensive because simple generators always run at the same speed.

      Does a generator lose power in the mountains?

      Yes. A combustion engine gets less oxygen at altitude, and warm air has a similar effect. Pramac states approx. 3.5 % less power per 305 m above sea level and approx. 1 % per 6 °C above 16 °C. This applies to all generators, even if the datasheet does not mention it – at 1500 m that is already about 17 % less.

      What does a DC generator need to be able to do?

      It must be started and controlled by the system controller – with Victron, the GX device – and the charge voltages must be freely adjustable. Otherwise it does not match the battery and problems follow.

      Note: This calculator provides an estimate based on nameplate data and guide values from practice. It does not replace a measurement on the system or professional advice. Liability for decisions based on the results is excluded to the extent permitted by law.